TLS2 Monitoring Systems
Part No. 577013-767, Revision H 130
Function Code: 8C6 Version 4
Function Type: Set TCP/IP Remote Port Number
Command Format: Inquire:
Display: <SOH>S8C600PPPPP <SOH>I8C600
Computer: <SOH>s8C600pppp <SOH>i8C600
Notes:
1. PPPPP - Remote Port (decimal)
2. pppp - Remote Port (ASCII Hex)
Typical Response Message, Display Format:
<SOH>
S8C600
JAN 31, 2008 9:02 AM
TCPIP SETUP PARAMETERS
REMOTE PORT NUMBER: 1200
<ETX>
Typical Response Message, Computer Format:
<SOH>s8C600YYMMDDHHmmvpppp&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. v - Valid Data Flag
0 = Not Valid
1 = Valid
3. pppp - Remote Port (ASCII Hex)
4. && - Data Termination Flag
5. CCCC - Message Checksum