EasyManuals Logo
Home>Veeder-Root>Measuring Instruments>TLS2

Veeder-Root TLS2 Serial Interface Manual

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #135 background imageLoading...
Page #135 background image
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 132
Function Code: 8C8 Version 4
Function Type: Set Email Recipient 2
Command Format: Inquire:
Display: <SOH>S8C800r..r <SOH>I8C800
Computer: <SOH>s8C800r..r <SOH>i8C800
Typical Response Message, Display Format:
<SOH>
I8C800
JAN 31, 2008 9:02 AM
TCPIP SETUP PARAMETERS
EMAIL RECIPIENT 2: JANEDOE@VEEDER.COM
<ETX>
Typical Response Message, Computer Format:
<SOH>s8C800YYMMDDHHmmvrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrr&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. v - Valid Data Flag
0 = Not Valid
1 = Valid
3. r - Email Recipient 2 (41 ASCII characters [20h-7Eh])
4. && - Data Termination Flag
5. CCCC - Message Checksum