EasyManuals Logo
Home>Veeder-Root>Measuring Instruments>TLS2

Veeder-Root TLS2 Serial Interface Manual

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #136 background imageLoading...
Page #136 background image
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 133
Function Code: 8C9 Version 4
Function Type: Set Email From
Command Format: Inquire:
Display: <SOH>S8C900fffffffffffffffffffffff <SOH>I8C900
Computer: <SOH>s8C900fffffffffffffffffffffff <SOH>i8C900
Typical Response Message, Display Format:
<SOH>
I8C900
JAN 31, 2008 9:02 AM
TCPIP SETUP PARAMETERS
EMAIL FROM: MYTLS2
<ETX>
Typical Response Message, Computer Format:
<SOH>s8C900YYMMDDHHmmvfffffffffffffffffffffff&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. v - Valid Data Flag
0 = Not Valid
1 = Valid
3. f - Email From (23 ASCII characters [20h-7Eh])
4. && - Data Termination Flag
5. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS2 and is the answer not in the manual?

Veeder-Root TLS2 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals