Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 151
Function Code: A22 Version 1
Function Type: Probe Leak Test Flags - Gross Test
Command Format:
Display: <SOH>IA22TT
Computer: <SOH>iA22TT
Typical Response Message, Display Format:
<SOH>
IA2201
22-05-01 15:13
TANK 1 REGULAR UNLEADED MAG GROSS LEAK TEST ANALYSIS REPORT
GROSS LEAK TEST FLAGS:
<ETX>
Typical Response Message, Computer Format:
<SOH>iA22TTYYMMDDHHmmTTpPPNNFFFF...
TTpPPNNFFFF...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. p - Product Code (single ASCII character, from 20 Hex - 7E Hex)
4. PP - Probe Type:
00 - Unknown (no further data follows for this probe)
03 - MAG
5. NN - Number of 4-character Flag sequences to follow (Hex)
6. FFFF - Flag sequence characters indicating which Flag bits are set
7. && - Data Termination Flag
8. CCCC - Message Checksum