Function Code: A30 Version 1
Function Type: Get Tank Profile and Full Volume
Command Format:
Display: <SOH>IA30TT
Computer: <SOH>iA30TT
Typical Response Message, Display Format:
<SOH>
IA3001
22-05-01 15:13
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS
1 REGULAR UNLEADED 1 PT 10000
<ETX>
Typical Response Message, Computer Format:
<SOH>iA30TTYYMMDDHHmmTTppFFFFFFFF
TTppFFFFFFFF&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. pp - Profile (HEX)
00 = 1 point
01 = 4 point
02 = Linear
03 = 20 point
4. FFFFFFFF - Full height volume (ASCII Hex IEEE float)
5. && - Data Termination Flag
6. CCCC - Message checksum