Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 13
Function Code: 09E Version 5
Function Type: Setup Password Log In
Command Format:
Display: <SOH>S09E00PPPPPPPPPPPPPPPP
Computer: <SOH>s09E00PPPPPPPPPPPPPPPP
Notes:
1. P - Setup Password (6 to 16 ASCII characters [20h-7Eh])
Typical Response Message, Display Format:
<SOH>
I09E00
07-12-09 09:43
SETUP PASSWORD LOG IN
COMM 1: LOGGED IN
<ETX>
Typical Response Message, Computer Format:
<SOH>s09E00YYMMDDHHmmpS&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. p - Port Number
3. S - Log In Status
0 = Logged Out
1 = Logged In
4. && - Data Termination Flag
5. CCCC - Message Checksum