Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 12
Function Code: 053 Version 1
Function Type: Stop In-Tank Leak Detect Test
Command Format:
Display: <SOH>S053TT
Computer: <SOH>s053TT
Typical Response Message, Display Format:
<SOH>
S05301
22-05-01 14:55
TANK PRODUCT LABEL
1 REGULAR UNLEADED LEAK TEST STOP
<ETX>
Typical Response Message, Computer Format:
<SOH>s053TTYYMMDDHHmmTTk&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. k - Status Flag - 0 = OFF, 1 = ON
4. && - Data Termination Flag
5. CCCC - Message Checksum