Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 19
Function Code 111 Notes: (Continued)
Typical Response Message, Computer Format:
<SOH>i11100YYMMDDHHmmAAccNNTTSSYYMMDDHHmm...
AAccNNTTSSYYMMDDHHmm&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. AA - Alarm/Warning Category:
00 - All Functions Normal
02 - Tank Alarm
14 - Auto-Dial Alarm
3. cc - Sensor Category
00 - Unused
4. NN - Alarm Type Number:
- If AA is 02 and NN is:
03 = Tank High Water Alarm
04 = Tank Overfill Alarm
05 = Tank Low Product Alarm
08 = Tank Invalid Fuel Level Alarm
09 = Tank Probe Out Alarm
11 = Tank Delivery Needed Warning
12 = Tank Maximum Product Alarm
13 = Tank Gross Leak Test Fail Alarm
14 = Tank Periodic Leak Test Fail Alarm
15 = Tank Annual Leak Test Fail Alarm
27 = Tank Cold Temperature Warning
- If AA is 14 and NN is:
02 = Autodial Failed Alarm
5. TT - Tank/Sensor Number
6. SS - Alarm State
01 = Alarm cleared
02 = Alarm occurred
7. YYMMDDHHmm - Date/Time Alarm state occurred
8. && - Data Termination Flag
9. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS2 and is the answer not in the manual?

Veeder-Root TLS2 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals