EasyManuals Logo

Veeder-Root TLS2 Serial Interface Manual

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 20
Function Code: 112 Version 1
Function Type: Non-Priority Alarm History Report
Command Format:
Display: <SOH>I11200
Computer: <SOH>i11200
Typical Response Message, Display Format:
<SOH>
I11200
22-05-01 14:56
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
NON PRIORITY ALARM HISTORY REPORT
ID DESCRIPTION ALARM TYPE STATUS DATE TIME
T 1 REGULAR UNLEADED PROBE OUT CLEAR 19-03-01 23:36
T 1 REGULAR UNLEADED PROBE OUT ALARM 19-03-01 23:36
<ETX>
Typical Response Message, Computer Format:
<SOH>i11200YYMMDDHHmmAAccNNTTSSYYMMDDHHmm...
AAccNNTTSSYYMMDDHHmm&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. AA - Alarm/Warning Category:
See explanation for "AA" in Function i11100
3. cc - Sensor Category
See explanation for "cc" in Function i11100
4. NN - Alarm Type Number:
See explanation for "NN" in Function i11100
5. TT - Tank/Sensor Number
6. SS - Alarm State
01 = Alarm cleared
02 = Alarm occurred
7. YYMMDDHHmm - Date/Time Alarm state occurred
8. && - Data Termination Flag
9. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS2 and is the answer not in the manual?

Veeder-Root TLS2 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals