Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 21
Function Code: 113 Version 1
Function Type: Active Alarm Report
Command Format:
Display: <SOH>I11300
Computer: <SOH>i11300
Notes:
1. This command will report ALL active alarms and warnings
regardless of their acknowledgement state. If there are
more than can be contained in the non-priority and priority
history storage areas, they will be reported here without
time and date stamps
Typical Response Message, Display Format:
<SOH>
I11300
22-05-01 14:56
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
ACTIVE ALARM STATUS
ID DESCRIPTION ALARM TYPE DATE TIME
T 1 REGULAR UNLEADED PROBE OUT 19-03-01 23:36
<ETX>
Typical Response Message, Computer Format:
<SOH>i11300YYMMDDHHmma..ab..bc..cd..dAAccNNTTYYMMDDHHmm...
AAccNNTTYYMMDDHHmm&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. a..a - Station Header 1: 20 ASCII characters
3. b..b - Station Header 2: 20 ASCII characters
4. c..c - Station Header 3: 20 ASCII characters
5. d..d - Station Header 4: 20 ASCII characters
6. AA - Alarm/Warning Category:
See explanation for "AA" in Function i11100
7. cc - Sensor Category
See explanation for "cc" in Function i11100
8. NN - Alarm Type Number:
See explanation for "NN" in Function i11100
9. TT - Tank/Sensor Number
10. YYMMDDHHmm - Alarm Date and Time
11. && - Data Termination Flag
12. CCCC - Message Checksum