Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 22
Function Code: 114 Version 1
Function Type: Cleared Alarm Report
Command Format:
Display: <SOH>I11400
Computer: <SOH>i11400
Typical Response Message, Display Format:
<SOH>
I11400
22-05-01 14:56
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
CLEARED ALARMS REPORT
ID DESCRIPTION ALARM TYPE STATUS DATE TIME
T 1 REGULAR UNLEADED PROBE OUT CLEAR 19-03-01 23:36
<ETX>
Typical Response Message, Computer Format:
<SOH>i11400YYMMDDHHmma..ab..bc..cd..dAAccNNTTSSYYMMDDHHmm...
AAccNNTTSSYYMMDDHHmm&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. a..a - Station Header 1: 20 ASCII characters
3. b..b - Station Header 2: 20 ASCII characters
4. c..c - Station Header 3: 20 ASCII characters
5. d..d - Station Header 4: 20 ASCII characters
6. AA - Alarm/Warning Category:
See explanation for "AA" in Function i11100
7. cc - Sensor Category:
See explanation for "cc" in Function i11100
8. NN - Alarm Type Number:
See explanation for "NN" in Function i11100
9. TT - Tank/Sensor Number
10. SS - Alarm State
01 = Alarm cleared
02 = Alarm occurred
11. YYMMDDHHmm - Clear Alarm Date and Time
12. && - Data Termination Flag
13. CCCC - Message Checksum