Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 23
Function Code: 117 Version 1
Function Type: Priority Alarm History Report II
Command Format:
Display: <SOH>I11700
Computer: <SOH>i11700
Typical Response Message, Display Format:
<SOH>
I11700
22-05-01 14:56
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
PRIORITY ALARM HISTORY REPORT
ID DESCRIPTION ALARM TYPE STATUS DATE TIME REPEAT
T 1 REGULAR UNLEADED PROBE OUT CLEAR 19-03-01 23:36 0
T 1 REGULAR UNLEADED PROBE OUT ALARM 19-03-01 23:36 0
<ETX>
Typical Response Message, Computer Format:
<SOH>iii700YYMMDDHHmmAAccNNTTSSYYMMDDHHmmaaaa...
AAccNNTTSSYYMMDDHHmmaaaa&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. AA - Alarm/Warning Category
See explanation for "AA" in Function i11100
3. cc - Sensor Category
See explanation for "cc" in Function i11100
4. NN - Alarm Type Number
See explanation for "NN" in Function i11100
5. TT - Tank/ Sensor Number
6. SS - Alarm State
01 B Alarm cleared
02 B Alarm occurred
7. YYMMDDHHmm - Date and Time first alarm occurred
8. aaaa - number of times alarm occurred (hex)
9. && - Data Termination Flag
10. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS2 and is the answer not in the manual?

Veeder-Root TLS2 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals