EasyManua.ls Logo

Veeder-Root TLS2 - Probe Field Wiring Connection; Sealing Field Connections

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 29
Function Code: 205 Version 1
Function Type: In-Tank Status Report
Command Format:
Display: <SOH>I205TT
Computer: <SOH>i205TT
Typical Response Message, Display Format:
<SOH>
I20501
22-05-01 14:57
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
STATUS REPORT
TANK
1 ALL FUNCTIONS NORMAL
<ETX>
Typical Response Message, Computer Format:
<SOH>i205TTYYMMDDHHmmTTnnAA...
TTnnAA...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. nn - Number of alarms active for tank (Hex, 00 = none)
4. AA - Active tank alarm type:
03 = Tank High Water Alarm
04 = Tank Overfill Alarm
05 = Tank Low Product Alarm
08 = Tank Invalid Fuel Level Alarm
09 = Tank Probe Out Alarm
11 = Tank Delivery Needed Warning
12 = Tank Maximum Product Alarm
13 = Tank Gross Leak Test Fail Alarm
14 = Tank Periodic Leak Test Fail Alarm
15 = Tank Annual Leak Test Fail Alarm
27 = Tank Cold Temperature Warning
5. && - Data Termination Flag
6. CCCC - Message Checksum