EasyManua.ls Logo

Veeder-Root TLS2 - Page 33

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 30
Function Code: 206 Version 1
Function Type: In-Tank Alarm History Report
Command Format:
Display: <SOH>I206TT
Computer: <SOH>i206TT
Typical Response Message, Display Format:
<SOH>
I20601
22-05-01 14:57
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
TANK ALARM HISTORY
TANK 1 REGULAR UNLEADED
PROBE OUT 19-03-01 23:36
<ETX>
Typical Response Message, Computer Format:
<SOH>i206TTYYMMDDHHmmTTnnYYMMDDHHmmaaaa...
TTnnYYMMDDHHmmaaaa...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. nn - Number of alarms in history for tank (Decimal, 00 = none)
4. YYMMDDHHmm - Date and time alarm occurred
5. aaaa - Type of alarm:
0003 = Tank High Water Alarm
0004 = Tank Overfill Alarm
0005 = Tank Low Product Alarm
0008 = Tank Invalid Fuel Level Alarm
0009 = Tank Probe Out Alarm
000B = Tank Delivery Needed Warning
000C = Tank Maximum Product Alarm
000D = Tank Gross Leak Test Fail Alarm
000E = Tank Periodic Leak Test Fail Alarm
000F = Tank Annual Leak Test Fail Alarm
001B = Tank Cold Temperature Warning
6. && - Data Termination Flag
7. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2