Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 32
Function Code 207 Notes: (Continued)
Typical Response Message, Computer Format:
<SOH>i207TTYYMMDDHHmmTTNNRRnnttYYMMDDHHmmhhhhhhhhVVVVVVVVpppppppp...
TTNNRRnnttYYMMDDHHmmhhhhhhhhVVVVVVVVpppppppp...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. NN - Number of Leak History Reports to Follow (Hex)
4. RR - Leak Report Type:
00 = Last Test Passed
01 = Fullest Test Passed
02 = Fullest Periodic Monthly Test Passed
5. nn - Leak History Number (1 - 12) for first Monthly Tests Passed
6. tt - In-Tank Leak Test Type:
00 = 0.2 gal/hr test
01 = 0.1 gal/hr test
02 = Gross (3 gal/hr)test
7. YYMMDDHHmm - In-Tank Leak Test Start Time
8. hhhhhhhh - Leak Test Duration in Hours (ASCII Hex IEEE float)
9. VVVVVVVV - Leak Test Volume (ASCII Hex IEEE float)
10. pppppppp - Leak Test Percentage of Full Volume (ASCII Hex IEEE float)
11. && - Data Termination Flag
12. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS2 and is the answer not in the manual?

Veeder-Root TLS2 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals