Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 33
Function Code: 208 Version 1
Function Type: In-Tank Leak Test Results Report
Command Format:
Display: <SOH>I208TT
Computer: <SOH>i208TT
Typical Response Message, Display Format:
<SOH>
I20801
22-05-01 14:57
PREVIOUS IN TANK LEAK TEST RESULTS
TANK 1 REGULAR UNLEADED
TEST TYPE START TIME RESULT RATE HOURS VOLUME
ANNUAL 19-05-01 02:00 INVALID 0.00 2.0 8120
PERIODIC 19-05-01 02:00 PASSED 0.00 2.0 8120
GROSS 19-05-01 02:00 PASSED 0.00 8120
<ETX>
Typical Response Message, Computer Format:
<SOH>i208TTYYMMDDHHmmTTNNttmmYYMMDDHHmmRRrrrrrrrrhhhhhhhhVVVVVVVV...
TTNNttmmYYMMDDHHmmRRrrrrrrrrhhhhhhhhVVVVVVVV...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. NN - Number of Results to Follow (Hex)
4. tt - In-Tank Leak Test Result Type:
00 = 0.2 gal/hr Test
01 = 0.1 gal/hr Test
02 = Gross (3 gal/hr) Test
5. mm - In-Tank Leak Manifold Status:
00 = Tank Not Manifolded During Leak Test
01 = Tank Manifolded During Leak Test
6. YYMMDDHHmm - Previous In-Tank Leak Test Start Time
7. RR - Previous In-Tank Leak Test Result:
00 = Test Invalid
01 = Test Passed
02 = Test Failed
8. rrrrrrrr - Test Rate (ASCII Hex IEEE float)
9. hhhhhhhh - Leak Test Duration in Hours (ASCII Hex IEEE float)
10. VVVVVVVV - Leak Test Volume (ASCII Hex IEEE float)
11. && - Data Termination Flag
12. CCCC - Message Checksum