Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 52
Function Code: 50D Version 1
Function Type: Set Print Temperature Compensation Flag
Command Format: Inquire:
Display: <SOH>S50D00f <SOH>I50D00
Computer: <SOH>s50D00f <SOH>i50D00
Typical Response Message, Display Format:
<SOH>
I50D00
22-05-01 14:59
PRINT TC VOLUMES
DISABLED
<ETX>
Typical Response Message, Computer Format:
<SOH>i50D00YYMMDDHHmmf&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. f - Print Temperature Compensation Flag
0 = Disable
1 = Enable
3. && - Data Termination Flag
4. CCCC - Message Checksum