Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 53
Function Code: 50E Version 1
Function Type: Set Temperature Compensation Value
Command Format: Inquire:
Display: <SOH>S50E00DDD.hh <SOH>I50E00
Computer: <SOH>s50E00FFFFFFFF <SOH>i50E00
Notes:
1. DDD.hh - Compensation Temperature, Degrees and hundredths (Decimal)
2. FFFFFFFF - Compensation Temperature, Degrees (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I50E01
22-05-01 14:59
TEMP COMPENSATION
VALUE (DEG F ): 59.0
<ETX>
Typical Response Message, Computer Format:
<SOH>i50E00YYMMDDHHmmFFFFFFFF&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. FFFFFFFF - Compensation Temperature, Degrees (ASCII Hex IEEE float)
3. && - Data Termination Flag
4. CCCC - Message Checksum