Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 54
Function Code: 50F Version 1
Function Type: Set System Date/Time Display Format
Command Format: Inquire:
Display: <SOH>S50F00xx <SOH>I50F00
Computer: <SOH>s50F00xx <SOH>i50F00
Typical Response Message, Display Format:
<SOH>
I50F00
22-05-01 14:59
DD-MM-YY HH:MM:SS
<ETX>
Typical Response Message, Computer Format:
<SOH>i50F00YYMMDDHHMMxx&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. xx - Display format for DATE/TIME code
01 - MON DD, YYYY HH:MM:SS xM (12 Hour Clock)
02 - MON DD YYYY HH:MM:SS (24 Hour Clock)
03 - MM-DD-YY HH:MM:SS xM (12 Hour Clock)
04 - MM-DD-YY HH:MM:SS (24 Hour Clock)
05 - DD-MM-YY HH:MM:SS (24 Hour Clock)
06 - YY-MM-DD HH:MM:SS (24 Hour Clock)
3. && - Data Termination Flag
4. CCCC - Message Checksum