Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 55
Function Code: 514 Version 1
Function Type: Set H-Protocol Height/Volume format
Command Format: Inquire:
Display: <SOH>S51400f <SOH>I51400
Computer: <SOH>s51400f <SOH>i51400
Typical Response Message, Display Format:
<SOH>
I51400
22-05-01 14:59
H-PROTOCOL DATA FORMAT
HEIGHT
<ETX>
Typical Response Message, Computer Format:
<SOH>i51400YYMMDDHHmmf&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. f - Data Format
0 = Height
1 = Volume
3. && - Data Termination Flag
4. CCCC - Message Checksum