Function Code: 536 Version 1
Function Type: Set RS-232 Security Code per Port
Command Format: Inquire:
Display: <SOH>S536PPsaaaaaa <SOH>I536PP
Computer: <SOH>s536PPsaaaaaa <SOH>i536PP
Notes:
1. PP - Port number (Decimal, 01-02; 99=this port)
2. s - Enable or Disable Status (if disabled no password is
required)
3. aaaaaa - Security code (6 ASCII characters from 20 hex - 7E Hex)
Typical Response Message, Display Format:
<SOH>
I53601
22-05-01 15:06
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
<ETX>
Typical Response Message, Computer Format:
<SOH>i536PPYYMMDDHHmmsaaaaaa&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. s - Status
00 = Disabled
01 = Enabled
3. aaaaaa - Security code (6 ASCII characters from 20 hex - 7E Hex)
4. && - Data Termination Flag
5. CCCC - Message Checksum