Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 66
Function Code: 539 Version 4
Function Type: Set Receiver Auto Dial On Events
Command Format: Inquire:
Display: <SOH>S539RRAANNTTSS <SOH>I539RR
Computer: <SOH>s539RRAANNTTSS <SOH>i539RR
Typical Response Message, Display Format:
<SOH>
I53901
22-05-01 15:06
RECEIVER EVENTS SETUP REPORT
RECEIVER : 01
IN-TANK EVENTS :
T 1:SHIFT CLOSE EVENT
<ETX>
Typical Response Message, Computer Format:
<SOH>i539RRYYMMDDHHmmRRnnAANNTTSS...
RRnnAANNTTSS&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. RR - Receiver Number (Decimal, 01 only)
3. nn - Number of Events to Follow (Hex)
4. AA - Event Category
02 - Tank Event
5. NN - Event Type Number:
- If AA is 02 and NN is:
01 = Tank Delivery Completed
02 = Shift Close Event (Version 4)
6. TT - Tank/Sensor Number (Decimal, 00 = all)
7. SS - Status (Hex)
00 = Clear
01 = Set
8. && - Data Termination Flag
9. CCCC - Message Checksum