Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 75
Function Code: 575 Version 5
Function Type: Set Dial Type
Command Format: Inquire:
Display: <SOH>S571RRDDDDDD <SOH>I571RR
Computer: <SOH>s571RRHHHHHHHH <SOH>i571RR
Notes:
1. DDDDDD - Site ID (Decimal)
Typical Response Message, Display Format:
<SOH>
I57500
JUL 8, 2009 9:02 AM
SITE ID
RCVR SITE ID
1 123456
<ETX>
Typical Response Message, Computer Format:
<SOH>i57500YYMMDDHHmmRRHHHHHHHH&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. RR - Receiver Number (Decimal)
3. HHHHHHHH - Site ID (Hex)
4. && - Data Termination Flag
5. CCCC - Message Checksum