Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 89
Function Code: 60C Version 1
Function Type: Set Tank Stick Height Offset
Command Format: Inquire:
Display: <SOH>S60CTTIII.hh <SOH>I60CTT
Computer: <SOH>s60CTTFFFFFFFF <SOH>i60CTT
Notes:
1. TT - Tank Number (Decimal, 00 = all)
2. III.hh - Stick Height Offset, Inches and hundredths (Decimal)
3. FFFFFFFF - Stick Height Offset, Inches (ASCII Hex IEEE float). Value
must be within the range of +144 to -144 inches. It is used
to calculate stick height = height (without tilt) + stick
offset
Typical Response Message, Display Format:
<SOH>
I60C01
22-05-01 15:08
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 REGULAR UNLEADED 1.25
<ETX>
Typical Response Message, Computer Format:
<SOH>i60CTTYYMMDDHHmmTTFFFFFFFF
TTFFFFFFFF&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. FFFFFFFF - Stick Height Offset, Inches (ASCII Hex IEEE float)
4. && - Data Termination Flag
5. CCCC - Message Checksum