EasyManua.ls Logo

Veeder-Root TLS2 - Page 91

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 88
Function Code: 60B Version 1
Function Type: Set Tank Stick Height Function Enable
Command Format: Inquire:
Display: <SOH>S60B00f <SOH>I60B00
Computer: <SOH>s60B00f <SOH>i60B00
Typical Response Message, Display Format:
<SOH>
I60B01
22-05-01 15:08
STICK HEIGHT OFFSET ENABLE STATUS
ENABLED
<ETX>
Typical Response Message, Computer Format:
<SOH>i60B00YYMMDDHHmmf&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. f - Stick Height Function:
0 = Disabled
1 = Enabled
3. && - Data Termination Flag
4. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2