Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 94
Function Code: 612 Version 1
Function Type: Set Tank Manifolded Partners
Command Format: Inquire:
Display: <SOH>S612TTttTTtt...<CR> <SOH>I612TT
Computer: <SOH>s612TTttTTtt...<CR> <SOH>i612TT
Typical Response Message, Display Format:
<SOH>
I61201
22-05-01 15:09
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL MANIFOLDED TANKS
1 REGULAR UNLEADED 3, 5
<ETX>
Typical Response Message, Computer Format:
<SOH>i612TTYYMMDDHHmmTTNNtt...
TTNNtt...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Number of the first tank to be manifolded
3. NN - Number of tanks that are manifolded together
4. tt - Tank numbers of other tanks to be manifolded to first tank
5. && - Data Termination Flag
6. CCCC - Message Checksum