EasyManua.ls Logo

Veeder-Root TLS2 - Page 98

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 95
Function Code: 61A Version 1
Function Type: Set In-Tank Leak Test Early Stop
Command Format: Inquire:
Display: <SOH>S61ATTf <SOH>I61ATT
Computer: <SOH>s61ATTf <SOH>i61ATT
Typical Response Message, Display Format:
<SOH>
I61A01
22-05-01 15:09
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 REGULAR UNLEADED DISABLED
<ETX>
Typical Response Message, Computer Format:
<SOH>i6A000YYMMDDHHmmTTf...
TTf&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. f - In-Tank Leak Test Early Stop Flag:
0 = DISABLED
1 = ENABLED
3. && - Data Termination Flag
4. CCCC - Message Checksum