41
7 Set up with the display and adjustment module
POINTRAC 31 • 8/16 mA/HART - four-wire
43388-EN-180322
Information:
The simulation is automatically terminated 10 minutes after the last
pressing of a key.
The sensor calculates a suitable integration time automatically.
Additional adjustments
In this menu item you can set the actual date, time and display format.
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language, SIL and HART mode.
The following reset functions are available:
Basic settings: Resetting of the parameter adjustments to default
valuesatthetimeofshipment.Order-specicsettingsaredeleted.
Default settings: Resetting of the parameter adjustment like under
"Basic settings". In addition, special parameters are reset to default
values.Order-specicsettingsaredeleted.
Peak values of measured value: Resetting of the parameter adjust-
ments in the menu item "Setup" to the default values of the respective
instrument.Order-specicsettingsremainbutarenottakenoverinto
the current parameters.
Peak values of temperature: Resetting of the measured min. and
max. temperatures to the actual measured value.
The following table shows the default values of the instrument. The
values apply for the application "Limit level". First of all you have to
select the application.
Depending on the instrument version, not all menu items may be
availableortheymaybedierentlyassigned:
Diagnosis - Calculated
damping
Additional settings - Date/
Time
Additional settings -
Reset