42
7 Set up with the display and adjustment module
POINTRAC 31 • 8/16 mA/HART - four-wire
43388-EN-180322
Menu Menu item Default value
Setup Measurement loop name Sensor
Isotope Cs-137
Application Limit level
Adjustment mode Single point adjustment
Adjustment - uncovered
90000 ct/s
Adjustment - covered 9000 ct/s
only with two-point adjustment
Delta I
90 %
Background radiation 0 ct/s
Temperature unit °C
Damping Is calculated automatically by the instrument
Current output mode
8/16 mA, < 3.6 mA
Mode - Relay Overllprotection
Lock adjustment Released
Display Language Selected language
Displayed value Pulse rate
Additional adjustments Temperature unit °C
HART mode Standard
With this function you can select the mode.
ThesensoroerstheHARTmodesstandardandmultidrop.
The default setting is standard with address 0.
If the measured value is outputted via the 4 … 20 mA output, you
must not switch over to HART Multidrop.
Themode'Standard',withxedaddress0(factorysetting),means
output of the measured value as 8/16 mA signal.
In Multidrop mode, several sensors are communicating on one two-
wire cable via the HART protocol.
In Multidrop mode, up to 15 sensors can be operated on one two-wire
cable. An address between 1 and 15 must be assigned to each sen-
sor.
With this function
Additional settings -
HART mode
Additional settings - Cop
y
instrument settings