Conguration Parameters Default Value Signicance and Adjustments
Standby diff.
Default value: 4°F (2°C)
Standby Temperature Differential
When Standby mode is set to ‘offset’, standby setpoints are calculated as follows:
Standby cool: Cool setpoint + Standby diff.
Standby heat: Heat setpoint - Standby diff.
Range: 1 to 5°F (0.5 to 2.5°C)
Fan cont. heat
Default value: On
Fan Control in Heating Mode
Congures the operation of the fan when system is heating.
On:Fan on
Off-Auto: Fan off if fan mode is auto
Off-All: Fan off
Choices: On, Off-Auto or Off-All