VT8350 [ User Interface Guide ]
PARAMETER DETAILS
Conguration Parameters Default Value Signicance and Adjustments
Enable
Default value: Off
Temperature Alarm Enabled
Enables wireless device to alert Room Controller if temperature value reaches
dened value in a particular paired device.
Choices: On or Off
Hysteresis
Default value: 2.0 °F (1.0 °C)
Temperature Alarm Hysteresis
Choices: 0 to 10 °F (0 to 5.5 °C)
Ambient high
Default value: 86.0 °F (30.0 °C)
Temperature Alarm Ambient High
Range: 75 to 122 °F (24 to 50 °C)
Ambient low
Default value: 40.0 °F (4.5 °C)
Temperature Alarm Ambient Low
Range: 32 to 45 °F (0 to 7 °C)
Refrig. high
Default value: 40.0 °F (4.5 °C)
Temperature Alarm Refrigerator High
(only present if a refrigeration sensor is installed)
Range: 32 to 50 °F (0 to 10 °C)
Refrig. low
Default value: 32.0 °F (0.0 °C)
Temperature Alarm Refrigerator Low
(only present if a refrigeration sensor is installed)
Range: 32 to 50 °F (0 to 10 °C)
Freezer high
Default value: 0.0 °F (-17.5 °C)
Temperature Alarm Freezer High
(only present if a freezer sensor is installed)
Range: -40 to 32 °F (-40 to 0 °C)
TEMPERATURE ALARMS CONFIGURATION
The Temperature Alarms Conguration screens show the values that trigger an alarm only for ZigBee wireless sensors with
temperature measurement.
1/2 Temperature
Enable Off
Hysteresis 1.0 °C
2/2 Temperature
Ambient high 30.0 °C
Ambient low 4.5 °C
Refrig. high
4.5 °C
Refrig. low 0.0 °C
Freezer high -17.5 °C