Low battery alarm
The inverter has switched off due to low battery voltage. The "low
battery" LED is blinking.
Temperature pre-alarm
The internal temperature is reaching a critical level. The
"temperature" LED is blinking.
Temperature alarm
The inverter has switched off due it's internal temperature being too
high. The "temperature" LED is on.
Overload pre-alarm and low battery pre-alarm
The battery is nearly exhausted and the nominal output of the
inverter is exceeded. The "overload" and "low battery" LEDs are
both blinking alternately,
Ripple pre-alarm
The ripple voltage on the battery terminals is too high. The
"overload" and "low battery" LEDs are both blinking simultaneously.
Ripple alarm
The inverter has switched off due to excess ripple voltage on the
battery terminals. The "overload" and "low battery" LEDs are both
on.
MultiPlus-II 48V 3kVA 120V
Page 7 Operation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Victron energy MultiPlus-II and is the answer not in the manual?

Victron energy MultiPlus-II Specifications

General IconGeneral
ModelMultiPlus-II
Inverter Power3000 VA
Output Power2400 W
Output Voltage230 VAC
Output Frequency50 Hz or 60 Hz
Charger Current35 A
Efficiency94%
Weight18 kg
Input Voltage230 VAC
Input Voltage Range187-265 VAC
PowerControl and PowerAssistYes
Battery Voltage48 V
Transfer Switch50 A
ProtectionOverload, Short Circuit, Over Temperature