Bulk charging
The AC input voltage is switched through and the charger operates
in bulk mode. The "bulk" LED is on.
BatterySafe
The mains voltage is switched through and the charger is on.
However, the set absorption voltage has not yet been reached. The
"bulk" and "absorption" LEDs are both on.
Absorption charging
The mains voltage is switched through and the charger operates in
absorption mode. The "absorption" LED is on.
Float charging
The mains voltage is switched through and the charger operates in
float mode. The "float" LED is on.
Equalize charging
The mains voltage is switched through and the charger operates in
equalize mode. The "bulk" and "absorption" LED are both blinking.
PowerControl
The AC input is switched through. The AC output current is equal
to the preset maximum input current. The charge current is
reduced to 0A. The "mains on" LED is blinking.
MultiPlus-II 48V 3kVA 120V
Page 8 Operation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Victron energy MultiPlus-II and is the answer not in the manual?

Victron energy MultiPlus-II Specifications

General IconGeneral
ModelMultiPlus-II
Inverter Power3000 VA
Output Power2400 W
Output Voltage230 VAC
Output Frequency50 Hz or 60 Hz
Charger Current35 A
Efficiency94%
Weight18 kg
Input Voltage230 VAC
Input Voltage Range187-265 VAC
PowerControl and PowerAssistYes
Battery Voltage48 V
Transfer Switch50 A
ProtectionOverload, Short Circuit, Over Temperature
CommunicationVE.Bus, VE.Direct