Vitodens 100-W, B1HE/B1KE Combi Installation/Service
Commissioning
IMPORTANT
Seal Test on Coaxial Flue System
(annular gap check)
Legend
A Combustion air aperture
If the test port is not sealed, combustion air is drawn in
from the room. After the leak test, re-seal the test port
with the plug.
For sealed combustion, coaxial vent only
Viessmann strongly recommends that the heating
contractor perform a simplified leak test during boiler
start-up. For this purpose it is sufficient to measure the
CO
2
concentration of the combustion air in the coaxial
gap of the air intake pipe. The vent pipe is considered
sufficiently leak-proof if a CO
2
concentration in the
combustion air no higher than 0.2% or an O
2
concentration
no lower than 20.6% is measured.
If higher CO
2
values or lower O
2
values are measured,
check venting system thoroughly.
Note: The vent pipe adaptor comes with two measurement
ports, one for combustion air intake measurement
and one for flue gas measurement.
Note: This test is not applicable for single-wall venting
systems (non-sealed combustion).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Viessmann B1KE Combi Series and is the answer not in the manual?

Viessmann B1KE Combi Series Specifications

General IconGeneral
BrandViessmann
ModelB1KE Combi Series
CategoryBoiler
LanguageEnglish

Related product manuals