Vitodens 100-W, B1HE/B1KE Combi Installation/Service
System Configuration (parameters)
General
(continued)
1098.5 “Calorific value”
Setting Explanations
10,0000
5.0000 to 40.0000
Value is provided on the gas supplier’s bill. Used for gas consumption data.
Calorific value adjustable from 5.0000 to 40.0000 kWh/m
3
in increments of 0.0001
If you don’t have a supplier’s bill
- Conversion factor for Natural Gas: 1kWh/m3=96.6 BTU/ft3
- Conversion factor for Liquid Propane Gas:25.8742 kWh/m3=2500 BTU/ft3
1504.0 “Source for date and time”
Setting Explanations
Local 0
1
Selection of source for date and time
The setting depends on the boiler and accessories.
Factory setting: The date and time are adopted from the control unit.
Internet protocol (see parameter “508.0”)
2241.0 “Source outside temperature sensor “
Setting Explanations
1 Hardwired
521.0 "Interval in burner hours run until next maintenance"
Setting Explanations
0
0 to 25500
Number of burner hours to run until next service
Burner hours until next service adjustable from 0 to 25500
522.3 “Interval until next maintenance”
Setting Explanations
0
1
2
3
4
5
Interval until next maintenance
No interval selected
3 months
6 months
12 months
18 months
24 months
596.0 “Maximum heating output”
Setting Explanations
100
0 to 100
A limit can be set on the maximum heating output for heating operation.
Heating output in the factory setting 100%
Adjustable from 0 to 100%
597.0 “Limit, max. heating output for DHW heating”
Setting Explanations
100
0 to 100
A limit can be set on the maximum heating output for DHW heating.
Heating output in the factory setting 100%
Adjustable from 0 to 100%
Boiler
Note: Parameter values in bold are factory settings.