25
Initial start-up/Configuration
The control unit has two setting ranges, which must be configured separately:
H General control unit (described in the menu as ”Function 001-A”)
for general data, such as date and time
H Multiple-boiler control unit (described in the menu as ”Function 001-B”)
for the control of a multiple-boiler system in which each boiler is activated based on operating hours and tem-
perature.
Both configurations must be completed.
The control unit will not function properly
if the c onfiguration is not complete.
First start up the gas-fired wall-mounted boilers,
then the cascade control!
General control unit
Condition: Access level 3 must be selected (see page 6).
Select ”Function General” with
if ”Function General” is not already displayed;
confirm with
.
Select ”Configuration” with
; confirm with .
Select ”Yes” with
/ ; confirm with .
Select the required language with
/ ; confirm with .
Select ”Yes” with
/ if you wish the time to change automatically between
summer- and wintertime; confirm with
.
Press
to return to ”Function General”.
The ”Function General” configuration is now completed.
5285 565 v1.35285 565 v1.3
IMPORTANT
Function 001-A
General
Configuration
Configure
Function Yes
English
Summer-/winter-
time switch Yes