Nominal value (multiple-boiler control unit)
In most cases this value corresponds to the set room temperature in normal mode.
With radiator systems, this value generally corresponds to the low end temperature.
A higher setting is recommended for convector heating systems.
Design temperature according to the geographical area.
Max. required supply temperature in accordance with the size of the heating surfaces.
The deflection factor of the heating curve must be adjusted according to the heating
surfaces used.
In the factory default setting, this value is set to 1.33 (radiator heating system).
Standard values for the deflection/curvature factor:
H Radiator heating system: 1.25 to 1.35
H Convector heating system: 1.40
H Underfloor heating system: 1.1
Minimum supply temperature.
Maximum supply temperature.
Supply temperature for external heat demand
If the ”external heat demand” contact is closed, the supply temperature will be raised to the nominal value.
Nominal value (multiple-boiler control unit)
Required supply temperature with closed contact.
In the ” Operating data” menu you can scan whether the control unit is set to “flowtemp set point”.
5285 565 v1.35285 565 v1.3
Outsidetemp
fixed point 20ºC
Flowtemp
fixed point 20ºC
Outsidetemp
climazone –10ºC
Flowtemp
climazone 80ºC
Heating curve:
curvature 1.33
Flowtemperature
minimum 1ºC
Flowtemperature
maximum 74ºC
Flowtemp
Desired 70ºC