2.3.4 Output Circuits
The panel has three types of output circuits.
Notification Appliance Circuit (NAC)
Releasing Appliance Circuit (RAC)
Potential Free Contact Relay Outputs (PFC)
NAC
No. of NAC : 3 circuits
Type : Class B
Output Voltage : 27.5 V max
Current : <250mA (each)
Terminals : J11
Wire Size : 1.5 Sq. mm.
RAC
No. of RAC : 2 circuits
Type : Class B
Output Voltage : 27.5 V max
Current : 500mA (each)
Terminals : J14
Wire Size : 1.5 Sq. mm. Twisted pair wire
Fixed Output (PFC)
Four PFC outputs: J13 on Interface board has 9 pins.