TSGR-21 GAS Release Panel User Manual
Vighnaharta Technologies Pvt. Ltd. Page 8 of 43
1.2 System Features:
Operated on 24 V/3A DC power supply.
Battery low voltage 23 V DC and battery cut at 22 V.
Stand by battery backup of up to 24 hrs.
16 x 2 alpha numeric LCD Display.
LED indications for various modes on front panel.
Local buzzer indication for fire, fault, and testing operation.
4 x 2 keypad for configuration and program the system.
Real time clock.
Programmable class B Initiating Device Circuits (IDCs) for smoke detectors & heat detectors.
Normal fire detection.
Zone Disable facility.
Automatic and manual RAC release is available.
Remote and manual release and abort is available.
Programmable Releasing Appliance Circuits (RACs).
Cross zone compatibility.
Three Notification Appliance Circuits (NACs).
Three PFC output one Fixed for fire, and two programmable relay for fault, Fire & RAC
released condition.
External digital inputs for RAC release, abort, and Configurable Remote Input for Remote Fire
and Remote Silence
Configurable time setting Manual release time, RAC pre release time, Solenoid off Time,
RAC Abort Time, NAC silence time.
Auto, Manual, Maintenance Key switch
Keypad Enable , disable and Evacuate though key switch.