EasyManua.ls Logo

VIPA SLIO Series - VIPA 007-1 AB00 Pin Assignment

VIPA SLIO Series
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2 Power modules Manual VIPA System SLIO
2-4 HB300E - PS-CM - Rev. 11/28
For wires with a cross section of 0.08mm
2
up to 1.5mm
2
.
2 6
3 7
4 8
1 5
1
2
3
4
5
6
7
8
26
37
48
15
PM
0V
DC24V
0V
DC24V
Pos. Function Type Description
1 --- --- not connected
2 DC 24V I Feed-in DC 24V
power section supply
3 0V I Feed-in ground GND
power section supply
4 --- --- not connected
5 --- --- not connected
6 DC 24V O DC 24V power section supply I/Os
7 0V O ground GND power section supply I/Os
8 --- --- not connected
I: Input, O: Output
Attention!
Since the power section supply is not internally protected, it is to be
externally protected with a fuse, which corresponds to the maximum
current. This means max. 10A is to be protected by a 10A fuse (fast)
respectively by a line circuit breaker 10A characteristics Z!
Please consider within wiring the maximum load current of the contacts.
With the System SLIO this is max. 10A.
Pin assignment