DS - Data set for access via CPU, PROFIBUS and PROFINET
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT
Name Bytes Function Default DS IX SX
DIAG_EN 1 Diagnostic interrupt* 00h 00h 3100h 01h
CH0A 1 Input frequency track A 02h 01h 3101h 02h
CH1B 1 Input frequency track B 02h 01h 3102h 03h
CH2L 1 Input frequency Latch 02h 01h 3103h 04h
CH3G 1 Input frequency Gate 02h 01h 3104h 05h
CH4R 1 Input frequency Reset 02h 01h 3105h 06h
CH5 1 0 (fix) 00h 01h 3106h 07h
INT_I 1 Interrupt behavior* 80h 80h 3107h 08h
FCT_I 1 Counter function* 40h 80h 3108h 09h
MODE2_I 1 Counter mode 2* 00h 80h 3109h 0Ah
MODE3_I 1 Counter mode 3* 00h 80h 310Ah 0Bh
END_I 4 End value 00h 81h 310Bh...
310Eh
0Ch
LOAD_I 4 Load value 00h 81h 310Fh...
3112h
0Dh
HYST_I 1 Hysteresis 00h 81h 3113h 0Eh
PULSE_I 1 Pulse 00h 81h 3114h 0Fh
*) This parameter may only be transferred at STOP state.
The counter is controlled via the internal gate (I gate). The I gate is
the sum of hardware (HW) and Software gate (SW), where the HW
gate evaluation may be deactivated via the parameterization.
HW gate:
Open (activate):
edge 0-1 at the gate input of the module
Close (de-activate):
edge 1-0 at the gate input of the module
SW gate:
Open (activate):
in user program by edge 0-1 SW_GATE_SET in the control word
Close (deactivate):
in user program by edge 0-1 SW_GATE_RESET in the control word
Parameters
Control counter
VIPA System SLIODeployment
Fast introduction
HB300 | FM | 050-1BA00 | GB | 14-36 40