1. If self-check fails, the indicator will keep red on. If the self-test fails, you need
to check it.
2. Is it determined that it is the cell voltage/temperature/communication
failure/CBMS parameter?
3. The alarm information can be observed on the monitor and display screen
4. Detect and repair voltage/temperature/communication faults, return to step 3
and retest in order
Step 6: Close all battery cabinets
Step 7: Start UPS
Step 8: Start each battery cabinet CBMS
Step 9: Check whether the CBMS parameters are completely consistent/GBMS parameter
setting are reasonable. If it makes sense, go to the next step. If it doesn't, recheck and
make changes.
Step 10: Check the dry contacts and verify that are reasonable. If it makes sense, go to the
next step. If it doesn't, re-check and confirm the cause (Contact our technical to redefine
dry contacts)
Step 11: Check whether the communication is normal, if it makes sense, go to the next
step. If it doesn't, check the register configuration and verification and retest.
Step 12: Test the backup time.