14  D-303169 KP-160 PG2 User’s Guide 
3.4 Bypassing Zones 
A zone can by bypassed by pressing the   key until the zone number is shown on the zone # 
display (marked "4" in the "Icon and Key Indications" Figure) followed by the   key. 
Notes: 
1. Zone bypassing on the KP-160 PG2 unit can be operated only if Bypass was enabled via 
the control panel (see PowerMaster Installer Guide, section 3.5.2 "Configuring 
Arming/Disarming and Exit/Entry Procedures"). 
2. For UL Listed product, manual bypass must be enabled.  
3.5 Controlling Home Automation Devices 
To configure the PGM and X-10 output functions, see the corresponding sections of the 
control panel’s Installer Guide (“OUTPUTS” menu) and User Guide (“SCHEDULER” menu). 
Step  X-10 device ON  PGM device ON  X-10 or PGM 
device OFF 
X-10 or  PGM 
device TOGGLE 
1 
 
(~2sec)
       
2 
…  
[P0 to P9]
 
…  
[00 to 99]
 
  
[PGM  P0 to 
P9] or [X-10 01 
to 99]
 
 
[PGM  P0 to 
P9] or [X-10 01 
to 99]
 
3 
 
 
 
 
Notes: 
1. Long press (more than 2 sec.) of the   button initiates the X-10 function and the 
PGM/X-10 display (marked "4" in the "Icon and Key Indications" Figure) will read "01". 
Short press of the   button initiates the PGM function and the PGM/X-10 display will 
read "P0" with the   key. This number is incremented by 1 upon each press of the   
key. 
2. X-10/PGM not to be enabled in UL Listed Product.. 
3. Automation not to be enabled in UL Listed Product.