Loading...
PM100 / 300 U
SER
M
ANUAL
S
PECIFICATION
VPN 98-052 P
AGE
27
Harmonics
Range 0 to 50
Bandwidth Fundamental 5Hz to 50kHz*
Harmonics 10Hz to 250kHz
Accuracy Fundamental Volts
±0.1% rdg ±0.1% rng ±10mV ±0.1%/kHz
Amps
±0.2% rdg ±0.1% rng ±1mA ±0.2%/kHz
Harmonics
±(0.2 ± 0.1/kHz)% of fundamental
THD
Range 0% to 999%
Accuracy
±0.4% rdg ± 0.1% / kHz
Integrator
Range 1min to 99hrs 59mins
Environment
Operating 0 to +40
o
C
Shipping -20 to +60
o
C
Safety Designed to comply with EN61010-1
Pollution Degree 2, Installation Category II
Power Source
110V 90V to 132V
230V 195V to 265V
Frequency 48Hz to 65Hz
MAX. VA 25VA
Fuse Type & Rating 315mAT
Dielectric Strength
Input - Case 4kV AC 50/60 Hz for 1 minute.
Input - Power Srce 4kV AC 50/60 Hz for 1 minute
Power Srce - Case 1.9kV DC for 1 minute
*5Hz to 20kHz for the PM300 in three-phase, three-wire and three-phase, four wire modes.