IR610 high performance vector control frequency inverter user manual Chapter 5 function code table
- 48 -
Functio
n code
Parameter name
Description
Default
P01.06
Maximum frequency
10.00600.00Hz
50.00Hz
P01.07
Upper limit frequency
control
0digital setting (set through P01.08)
1AI1
2AI2
3Reserved
4Reserved
5Pulse setting HDI
6Reserved
7Communication setting
0
P01.08
Upper limit frequency
Lower limit frequency(P01.09)maximum
frequency (P01.06)
50.00Hz
P01.09
Lower limit frequency
0.00Hzupper limit frequency
0.00Hz
P01.10
Action when set
frequency lower than
lower limit frequency
0Run at low limit frequency
1Stop after delaying P01.11
2Run at zero speed
The inverter will coast to stop when the set
frequency is lower than the lower-limit one.if
the set frequency is above the lower limit one
again and it lasts for the time set byP01.11, the
inverter will come back to the running state
automatically.
0
P01.11
Delay time when set
frequency lower than
lower limit frequency
0.000s30.000s
This function code determines the hibernation
delay time. When the running frequency of the
inverter is lower than the lower limit one, the
inverter will stop to stand by.
When the set frequency is above the lower limit
one again and it lasts for the time set by
P01.11, the inverter will run automatically.
0.000s