Operation LTV
5.7 Resetting the Maintenance Timers – DeepSea
Background
The maintenance timers are preset on the controller. When the timer expires, the
alarm will display in the upper right corner of the screen. The maintenance timers
are preset as follows:
Oil change interval: 750 hours
Air filter change interval: 250 hours
Fuel filter change interval: 500 hours
Procedure
After the required maintenance has been completed, perform the following
procedure to reset a maintenance timer.
1. Use the up and down arrows (a) to navigate to the applicable screen.
2. Press and hold the “Stop” button (b) for 10 seconds. The timer will reset.
b
a
wc_gr012367