EasyManua.ls Logo

Watlow ez-zone pm - Page 23

Watlow ez-zone pm
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watlow EZ-ZONE
®
PM Integrated Controller 20 Chapter 2 Install and Wire
Communications Terminal Function Configuration
CB
CA
CC
CB
CA
C5
C3
C2
CB
CA
CC
CB
CA
C5
C3
C2
Modbus RTU EIA-485 T+/R+
Modbus RTU EIA-485 T-/R-
Modbus RTU EIA-485 common
Modbus RTU EIA-485 T+/R+
Modbus RTU EIA-485 T-/R-
Modbus RTU EIA-232 common
Modbus RTU EIA-232 to DB9 pin 2
Modbus RTU EIA-232 to DB9 pin 3
Modbus RTU 232/485 Communications
Slot B: PM6 _ _ _ _ - [
2] A A A
_ _ _
Slot E: PM[4,8,9] _ _ _ _ - [
2] _ _ _
_ _ _
V+
CH
SH
CL
V-
V+
CH
SH
CL
V-
DeviceNet™ power
Positive side of DeviceNet™ bus
Shield interconnect
Negative side of DeviceNet™ bus
DeviceNet™ power return
DeviceNet™ Communications
Slot B: PM6 _ _ _ _ - [
5] A A A
_ _ _
Slot E: PM[4,8,9] _ _ _ _ - [
5]
_ _ _ _ _ _
E8
E7
E6
E5
E4
E3
E2
E1
E8
E7
E6
E5
E4
E3
E2
E1
EtherNet/IP™ and Modbus TCP unused
EtherNet/IP™ and Modbus TCP unused
EtherNet/IP™ and Modbus TCP receive -
EtherNet/IP™ and Modbus TCP unused
EtherNet/IP™ and Modbus TCP unused
EtherNet/IP™ and Modbus TCP receive +
EtherNet/IP™ and Modbus TCP transmit -
EtherNet/IP™ and Modbus TCP transmit +
Ethernet 10/100 supporting EtherNet/IP™
and Modbus TCP
Slot B: PM6 _ _ _ _ - [
3] A A A
_ _ _
Slot E: PM[4,8,9] _ _ _ _ - [
3]
_ _ _ _ _ _
VP
B
A
DG
trB
B
A
trA
VP
B
A
DG
trB
B
A
trA
Voltage Potential
EIA-485 T+/R+
EIA-485 T-/R-
Digital ground (common)
Termination resistor B
EIA-485 T+/R+
EIA-485 T-/R-
Termination resistor A
Profibus Communications
Slot B: PM6 _ _ _ _ - [
6] A A A
_ _ _
Slot E: PM [4, 8, 9] _ _ _ _- [6] A A A A A A
Slot A Slot B Slot D Slot E
Terminal Definitions for Slot C.
Slot C Terminal Function Configuration
98
99
Power input: ac or dc+
Power input: ac or dc-
all
CC
CA
CB
Standard Bus or Modbus RTU EIA-485 common
Standard Bus or Modbus RTU EIA-485 T-/R-
Standard Bus or Modbus RTU EIA-485 T+/R+
Standard Bus or Modbus
PM _ _ _ _ _ - [1] _ _ _ _ _ _
CF
CD
CE
Standard Bus EIA-485 common
Standard Bus EIA-485 T-/R-
Standard Bus EIA-485 T+/R+
PM _ _ _ _ _ - [A,D,2,3,5] _ _ _ _ _ _
B5
D6
D5
Digital input-output common
Digital input or output 6
Digital input or output 5
PM _ _ [2] _ _ - _ _ _ _ _ _ _
PM _ _ [4] _ _ - _ _ _ _ _ _ _
A
Output 2
Output 1
Input 1
B
Output 3
Output 4
Input 2
D
Digital I/O 7 - 12
E
Communications Card
C
Dig I/O 5 & 6
485 Comms
Power
Back View
Slot Orientation
1/8 DIN Horizontal PM9
C
Dig I/O 5 & 6
485 Comms
Power
E
Communications Card
A
Output 2
Output 1
Input 1
B
Output 3
Output 4
Input 2
D
Digital I/O 7 - 12
Back View
Slot Orientation 1/8
DIN Vertical PM8

Table of Contents

Other manuals for Watlow ez-zone pm

Related product manuals