EasyManua.ls Logo

Watlow ez-zone pm - Output 2, 4 Mechanical Relay, Form a; Output 2, 4 Solid-State Relay, Form a; Quencharc Wiring Example

Watlow ez-zone pm
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watlow EZ-ZONE
®
PM Integrated Controller 28 Chapter 2 Install and Wire
Warning:
Óç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12 AWG)
single-wire termination or two 1.31
mm
2
(16 AWG)
• 0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals.
Note:
Maintain electrical isolation between
analog input 1, digital input-outputs,
switched dc/open collector outputs
and process outputs to prevent ground
loops.
Note:
The control output common terminal
and the digital common terminal are
referenced to different voltages and
must remain isolated.
Note:
This Equipment is suitable for use in
CLASS I, DIVISION 2, Groups A, B,
C and D or Non-Hazardous locations
only. Temperature Code T4A
Warning:
ç
Explosion Hazard Substitution of
component may impair suitability for
CLASS I, DIVISION 2.
Warning:
ç
Explosion Hazard - Do not disconnect
while the circuit is live or unless the
area is known to be free of ignitable
concentrations of flammable sub-
stances.
Output 2, 4 Mechanical Relay, Form A
common
normally open
L_
K_
Slot A, B
• 5Aat240VÅ (ac) or 30VÎ (dc)
maximum resistive load
• 20mAat24Vminimumload
• 125VApilotduty@120/240VÅ
(ac), 25 VA at 24VÅ (ac)
• 100,000cyclesatratedload
• Outputdoesnotsupplypower.
• forusewithacordc
See Quencharc note.
Output 1: (L2, K2)
PM _ _ _ _ [J] - _ _ _ _ _ _ _
Output 3: (L4, K4)
PM _ _ _ _ _ - _ _ _ [J] _ _ _
L
_
K
_
Output 2, 4 Solid-State Relay, Form A
common
normally open
L_
K_
Slot A, B
• 0.5Aat20to264VÅ (ac) maxi-
mum resistive load
•20VA120/240VÅ (ac) pilot duty
•opto-isolated,withoutcontact
suppression
• maximumoffstateleakageof
105 microamperes
• Outputdoesnotsupplypower.
• Donotuseondcloads.
See Quencharc note.
Output 1: (L2, K2)
PM _ _ _ _ [K] - _ _ _ _ _ _ _
Output 3: (L4, K4)
PM _ _ _ _ _ - _ _ _ [K] _ _ _
L
_
K
_
Quencharc Wiring Example
In this example the Quencharc circuit (Watlow
part# 0804-0147-0000) is used to protect PM
internal circuitry from the counter electro-
magnetic force from the inductive user load
when de-engergized. It is recommended that
this or an equivalent Quencharc be used when
connecting inductive loads to PM outputs.
Quencharc
User Load
L
_
K
_
N
1.1
0
-20
50
40
30
20100
-10
60 70
Amps RMS
Ambient Temperatue (
o
C)
0.1
1
0.2
0.9
0.3
0.4
0.5
0.6
0.7
0.8
1 Amp SSR Derating Curve
Safe Operating Area
Quencharc Note:
Switching pilot duty inductive
loads (relay coils, solenoids,
etc.) with the mechanical
relay, solid state relay or
open collector output options
requires use of an R.C. sup-
pressor.

Table of Contents

Other manuals for Watlow ez-zone pm

Related product manuals