Watlow EZ-ZONE
®
PM Integrated Controller 22 Chapter 2 Install and Wire
Warning:
Óç
Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.
Note:
Maximum wire size termination and
torque rating:
• 0.0507 to 3.30 mm
2
(30 to 12 AWG)
single-wire termination or two 1.31
mm
2
(16 AWG)
• 0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled
differently, depending on the model
number.
Note:
To prevent damage to the control-
ler, do not connect wires to unused
terminals.
Note:
Maintain electrical isolation between
analog input 1, digital input-outputs,
switched dc/open collector outputs
and process outputs to prevent ground
loops.
Note:
The control output common terminal
and the digital common terminal are
referenced to different voltages and
must remain isolated.
Note:
This Equipment is suitable for use in
CLASS I, DIVISION 2, Groups A, B,
C and D or Non-Hazardous locations
only. Temperature Code T4A
Warning:
ç
Explosion Hazard Substitution of
component may impair suitability for
CLASS I, DIVISION 2.
Warning:
ç
Explosion Hazard - Do not disconnect
while the circuit is live or unless the
area is known to be free of ignitable
concentrations of flammable sub-
stances.
Low Power
Power
power
power
98
99
CF
CD
CE
B5
D6
D5
Slot C
fuse
• Minimum/MaximumRatings
• 12to40VÎ (dc)
• 20to28VÅ (ac) Semi Sig F47
• 47to63Hz
• 14VAmaximumpowerconsumption(PM4,8and9)
• 10VAmaximumpowerconsumption(PM6)
PM_ _ [3,4] _ _ - _ _ _ _ _ _ _
High Power
Power
power
power
98
99
CF
CD
CE
B5
D6
D5
Slot C
fuse
• Minimum/MaximumRatings
• 85to264VÅ (ac)
• 100to240VÅ (ac) Semi Sig F47
• 47to63Hz
• 14VAmaximumpowerconsumption(PM4,8and9)
• 10VAmaximumpowerconsumption(PM6)
PM_ _ [1,2] _ _ - _ _ _ _ _ _ _
Digital Input 5 - 6
Digital Input
• Updaterate10Hz
• Drycontactordcvoltage
DC Voltage
• Inputnottoexceed36Vat3mA
• Inputactivewhen>3V@0.25mA
• Inputinactivewhen<2V
Dry Contact
• Inputinactivewhen>500Ω
• Inputactivewhen<100Ω
• maximumshortcircuit13mA
PM _ _ [2,4] _ _-_ _ _ _ _ _ _
Voltage Input
B
common
Vdc
D
_
_
Dry Contact
B
common
24 Vdc
_
_
D
Warning:
ç
Explosion Hazard - Dry contact closure
Digital Inputs shall not be used in Class
I Division 2 Hazardous Locations unless
switch used is approved for this ap-
plication.
98
99
CF
CD
CE
B5
D6
D5
Slot C
DC Input
common
DC Input

Table of Contents