Watlow EZ-ZONE
®
PM Integrated Controller 41 Chapter 5 Operations Page
Operations Page
Display
Parameter name
Description
Range Default
Parameter
Appears in
Menu When
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[``o;u]
[ o.v]
Linearization (1 to 2)
Output Value
View the value of this
function's output.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
Always Instance 1
Map 1 Map 2
- - - - 3572
Instance 2
Map 1 Map 2
- - - - 3642
0x86 (134)
1 to 2
7
- - - - float
R
No Dis-
play
Linearization (1 to 2)
Output Error
View reported cause
for Linearization out-
put malfunction.
None (61)
Open (65)
Shorted (127)
Measurement error
(140)
Bad calibration data
(139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
None - - - - Instance 1
Map 1 Map 2
- - - - 3614
Instance 2
Map 1 Map 2
- - - - 3684
0x86 (134)
1 to 2
0x1C (28)
- - - - uint
R
[``Pu]*
[oPEr]
Process Value Menu
[`Su;A]
[ Sv.A]
Process Value (1 to 2)
Source Value A
View the value of
Source A.
Linearization 1 is con-
nected to Source A of
Process Value 1
Linearization 2 is con-
nected to Source A of
Process Value 2
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
Always if
part number
digit 3 is C,
R, J, B, E
or N.
PM8 and 9
only
Instance 1
Map 1 Map 2
- - - - 3310
Instance 2
Map 1 Map 2
- - - - 3380
0x7E (126)
1 to 2
0x10 (16)
- - - - float
R
[`Su;b]
[ Sv.b]
Process Value (1 to 2)
Source Value B
View the value of
Source B.
Linearization 2 is con-
nected to Source B of
Process Value 1
Linearization 1 is con-
nected to Source B of
Process Value 2
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
Process Val-
ue Function
(Setup Page)
is not set to
Off or Square
Root.
Instance 1
Map 1 Map 2
- - - - 3312
Instance 2
Map 1 Map 2
- - - - 3382
0x7E (126)
1 to 2
0x11 (17)
- - - - float
R
[oFSt]
[oFSt]
Process Value (1 to 2)
Offset
Set an offset to be ap-
plied to this function's
output.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
0 Always Instance 1
Map 1 Map 2
- - - - 3324
Instance 2
Map 1 Map 2
- - - - 3394
0x7E (126)
1 to 2
0x17 (23)
- - - - float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E: EE-
PROM
S: User